RUI/Gateway

42

Chapter 5 Networking with a Gateway

Saving Settings to Non-volatile Memory

When save to EEPROM is enabled, values are saved

once every five seconds if a value written has changed.

if the EEPROM is disabled, any changes from the key-

pad that cause a change in the controller will initiate

a save of all values.

If controller settings are entered from the front

panel (PM) or via an RUI, changes are always saved to

non-volatile memory (EEPROM) in the controller (RM,

PM or ST). If the controller loses power or is switched

off, its settings will be restored when power is reap-

plied.

The EEPROM will wear out after about 1,000,000

writes, which should not be a problem with changes

made from the panel or RUI. However, if the controller

is receiving data from a Master device on a network

such as a PLC via the gateway, the EEPROM could

over time, wear out.

By default, settings made over Standard Bus (Com

instance 1) via the gateway or front panel of the RUI

are saved to EEPROM. Whenever new information

is sent from these devices, e.g., new set point, new

control mode, etc... a write to EEPROM will occur. No

further writes to EEPROM will occur until the input

data changes again. This would be true over a network

(Com instance 2) as well. If the data is changing it

will be written to the EEPROM. If it is desired to in-

hibit writes to the EEPROM over a network, write the

value of 59 to the addresses in the controllers specified

below.

Note:

This is an individual operation on each EZ-ZONE

controller on the Standard Bus side of the network.

CIP (DeviceNet and EtherNet/IP) by Con-

troller Type

For the following controllers:
RMC, RMS, RML, RMH, ST and PM-PID
Class = 150

Instance = 1

Attribute = 8

RMA
Class = 150

Instance = 2

Attribute = 8

PMI and PML
Class = 150

Class = 150

Instance = 1 Instance = 2

Attribute = 8 Attribute = 8

Modbus Registers by Controller Type

PMI and PML

Instance 1

Instance 2

Map 1 = 2494

Map 1 = 2514

Map 2 = 2974

Map 2 = 2994

PID

Instance 1
Map 1 = 2494
Map 2 = 2974

ST

Map 1 = 317
Map 2 = 2064

RMC RMA RMS RML RMH
2834 444 3474 3504 6514

Profibus by Controller Type

RMC, RML, RMH, PML, PMI and PID
198

RMS
112

RMA
82
Enumerated values for this member follows:
Yes = 106 (allow writes to EEPROM), No = 59 (Disable

writes to EEPROM)

Note:

Some controllers have only 1 communications port

where this discussion would apply if connected to

an RUI/GTW or RMA module. Other controls like

the PMI and the PML can have 2 communications

ports therefore you will find 2 instances. This setting

relates to the controller the RUI/GTW is connected

to, not the RUI/GTW itself. Everything changed in

the RUI/GTW, either via EZ-ZONE Configurator

software or from the front panel will be saved to the

EEPROM in the RUI/GTW.

Advertising