Disabling control, Disabling control 157 – Watlow PPC-2000 User Manual

Page 183

Advertising
background image

PPC-2000 User’s Guide

Chapter 4: Troubleshooting

Doc.# 30002-00 Rev 2.3

Watlow Anafaze

157

ç

CAUTION!

Do not perform this procedure at a time during which
closed-loop control and logic program outputs
should not be turned off.

1.

Remove power from the PPC-2000 system.

2.

Note the setting of the rotary switch on the Processor
Module.

3.

Set the rotary switch to position

E

.

4.

Power up the PPC-2000 system.

5.

Wait five seconds.

6.

Remove power from the PPC-2000 system.

7.

Set the rotary switch back to the position noted in Step 2.

8.

Power up the PPC-2000 system.

Disabling Control

If the settings in a PPC are not known it may be desirable to
power up the system in a state that will not generate outputs.
The following procedure describes how to power up the PPC-
2000 such that the closed-loop control and logic program, if any,
do not automatically begin:

ç

CAUTION!

Do not perform this procedure at a time during which
closed-loop control and logic program outputs
should not be turned off.

1.

Remove power from the PPC-2000 system.

2.

Note the setting of the rotary switch on the Processor
Module.

3.

Set the rotary switch to position

H

.

4.

Power up the PPC-2000 system.

5.

Set channels to the desired control modes to begin closed-
loop control.

6.

Click the Start Logic button on the PPC Globals screen to
start the logic program, if desired.

Advertising