Table 5.62 system error log – Watlow PPC-2000 User Manual

Page 245

Advertising
background image

PPC-2000 User’s Guide

Chapter 5: LogicPro and Modbus Reference

Doc.# 30002-00 Rev 2.3

Watlow Anafaze

217

Table 5.62

System Error Log

Data-

base

Offset

Modbus

Address

Name

Description

1

33201

Error Count

Total error count (255 maximum)

22

33222

Logic Checksum

Bad checksum in a logic program hex record

24

33224

Logic Load

Error verifying programming of a logic program hex
record

42

33242

Undefined Parm#

Parameter number outside the range of the database

43

33243

Bad Data Sent

Attempt to write data outside of a parameter’s range

44

33244

Bad Offset

Parameter offset beyond last element of the parameter

45

33245

Parm Size

Internal error in parameter size during read or write

47

33247

Database Reg

Internal error registering database entry

48

33248

Write to RO

Attempt was made to write to a read only variable

49

33249

Change Q Overflow

Overflow in database change queue

51

33251

Bad Flash Type

Flash type was not found in table

52

33252

Flash Overflow

Attempted write past end of flash

53

33253

Program Verify

Failed program verify test

61

33261

Bad Interrupt

Received bad interrupt

66

33266

Divide by Zero

Divide by zero exception

67

33267

Illegal OpCode

Illegal opcode exception

71

33271

AI Address

Multiple AI boards detected at one address

73

33273

AI Cal Data

AI board has invalid calibration data

74

33274

AI Timeout

System unable to process AI input on time

75

33275

CMO or Open T/C

CMO or OTC occurred on an AI channel

92

33292

Bad Baud Rate

Configured baud rate not supported

93

33293

UART Not Found

A UART not detected

94

33294

Wrong Port

Internal error: attempt to configure unsupported port

96

33296

Closed Port

Internal error: attempt to access port that isn’t open

97

33297

Bad Parity

Internal error: attempt to configure unsupported parity

101

33301

Bad CRC

Modbus message CRC did not match

102

33302

Bad Modbus Func

Modbus message attempted unsupported function

103

33303

Invalid Address

Invalid Modbus register address

104

33304

Pckt Ln or Func

Bad Modbus packet length or diagnostic subfunction

107

33307

Packet Length

Bad Modbus packet length

108

33308

Bad Address

Bad Modbus register address

111

33311

Missed I/O Update

Internal error: missed I/O update deadline

129

33329

Bad Error Msg

Internal error: attempted to post error of 128 or greater

Advertising