Examples, Read examples, Read examples 280 – Watlow PPC-2000 User Manual

Page 308

Advertising
background image

Appendix A: Modbus Protocol

PPC-2000 User’s Guide

280

Watlow Anafaze

Doc.# 30002-00 Rev 2.3

Examples

Read Examples

The data read must be sequentially located. When reading a
coil rather than a register, the address must be offset by the
location of the bit to read. Table A.3 shows the query and Table
A.4
shows the response:

Table A.3

Sample Packet for Host Query

Table A.4

Sample Packet for Slave Response

Example

Slave

Address

Function

Start

Address

High

Start

Address

Low

Number

of

Points

High

Number

of

Points

Low

CRC

Reading PV of
loop 2 controller 1
(single point read)

01

04

0B

B9

00

01

E2

0B

Reading loops 4
& 5 (primary) out-
put% of controller
3 (multipoint read)

03

03

18

9F

00

02

F3

67

Reading digital
input 4 to 13,
controller 1
(input status read)

01

01

0B

BB

00

10

4F

C7

Example

Slave

Address

Function

Byte

Count

Data1

High

Data1

Low

Data2

High

Data2

Low

CRC

Reading PV of
loop 2 (1600),
controller 1 (single
point read)

01

04

02

06

40

BB

60

Reading loops 4 &
5 (primary) out-
put% (50%, 60%),
of controller 3

03

03

04

01 F4 02

58

99

67

Reading digital
input 4 to 13,
controller 1 (input
status read)

01

01

02

08

00

BE

3C

Advertising