PPC-2000 User’s Guide

Chapter 2: Hardware Installation

Doc.# 30002-00 Rev 2.3

Watlow Anafaze

35

ç

CAUTION!

Power, input or output circuits with hazardous voltage
levels should not have any live accessible parts.

Wiring Recommendations

Keep the following guidelines in mind when selecting wires and
cables:

•

Use stranded wire. (Solid wire can be used for fixed
service; but it makes intermittent connections when you
move it for maintenance.)

•

Use #20 AWG TC extension wire. Larger or smaller sizes
may be difficult to install, may break easily, or may cause
intermittent connections.

•

Use shielded wire. (The electrical shield protects the
signals and the PPC-2000 from electrical noise.) Connect
only one end of the shield to earth ground.

•

Use copper wire for all connections other than
thermocouple sensor inputs.

See Table 2.9 for cable recommendations.

Table 2.9

Cable Recommendations

Noise Suppression

The PPC-2000’s outputs are designed to drive resistive loads.
Open collector outputs can drive solid state relays. These relays
may in turn operate more inductive types of loads such as

Function

Mfr. P/N

No. of

Wires

AWG

Gauge

Max.

Length

Analog Inputs

Belden #9154
Belden #8451

2
2

20
22

RTD Inputs

Belden #8772
Belden #9770

3
3

20
22

TC Inputs

TC Ext. Wire

2

20

Digital PID Outputs
and Digital I/O

Belden #9539
Belden #9542

9

20

24
24

Analog Outputs

Belden #9154
Belden #8451

2
2

20
22

Computer
Communication:
RS232, RS422,
RS485, or 20mA

Belden #9729
Belden #9730
Belden #9842
Belden #9843
Belden #9184

4
6
4
6
4

24
24
24
24
22

4000 ft.

4000 ft.

6000 ft.