PPC-2000 User’s Guide

Chapter 5: LogicPro and Modbus Reference

Doc.# 30002-00 Rev 2.3

Watlow Anafaze

175

* 16-bit binary number

NOTE!

Refer to Setting up Control Channels on page 92 for
the basics of setting up closed-loop control channels.

Process Variable Source (PV Source)

This variable determines the input used as the process variable
for this channel. The process variable is a hardware input
converted to engineering units. A value of 0 indicates a channel
with no input. See Table 5.13 on page 176 through Table 5.17
on page 179
for a list and explanation of input numbering.

Cool Limit Time

49

0-32767

41401-41450

578-5A9

Sensor Fail Heat%

37

0-1000

41001-41050

3E8-419

Sensor Fail Cool%

52

0-1000

41551-41600

60E-63F

Heat Output Filter

31

0-100

40701-40750

2BC-2ED

Cool Output Filter

46

0-100

41251-41300

4E2-513

Heat Output%

36

0-1000

40951-41000

3B6-3E7

Cool Output%

51

0-1000

41501-41550

5DC-60D

Heat Output Destination

40

0-4102

41151-41200

47E-4AF

Cool Output Destination

55

0-4102

41701-41750

6A4-6D5

Alarm Parameters

Alarm Status Flags

82

*

45451-45500

154A-157B

See

Table 5.28 on page 190

Alarm Control Flags

85

*

45601-45650

15E0-1611

See Table 5.30 on page 192

Alarm Acknowledge
Flags

88

*

45751-45800

1676-16A7

See Table 5.31 on page 192

Alarm Enable Flags

91

*

45901-45950

170C-173D

See Table 5.32 on page 192

High Process Limit

80

45351-45400

14E6-1517

See explanation on p. 193

Low Process Limit

83

45501-45550

157C-15AD

High Deviation Offset

86

45651-45700

1612-1643

Low Deviation Offset

89

45801-45850

16A8-16D9

Alarm Deadband

92

0-255

45951-46000

173E-176F

Alarm Delay

93

0-100

46001-46050

1770-17A1

High Process Output
Destination

81

0-336

3103-4102

45401-45450

1518-1549

Low Process Output
Destination

84

0-336

3103-4102

45551-45600

15AE-15DF

High Deviation Output
Destination

87

0-336

3103-4102

45701-45750

1644-1675

Low Deviation Output
Destination

90

0-336

3103-4102

45851-45900

16DA-170B

Parameter

#

Range

Modbus

Address

Hex

Address

Notes