<3. Parameter Setting>

3-9

IM 01C25R05-01EN

• Procedure to call up the display

[Root Menu] → Basic setup → Others →

→ H/L Swap

Select “Normal” or “Reverse”

3.4

Detailed Setup

3.4.1 Static Pressure Setup

(1) Selection of Gauge pressure and Absolute

pressure

Either the gauge pressure or absolute pressure can

be selected to display on the LCD display.

Absolute pressure is selected when the instrument

is shipped.

• Procedure to call up the display

[Root Menu] → Detailed setup → Signal condition →

SP Setup →
→ A / G Select Select “Gauge” or “Absolute”

(2) Selection of pressure side
Either the high or low pressure side of capsule can

be selected to monitor the static pressure.

High pressure side is selected when the instrument

is shipped.

• Procedure to call up the display

[Root Menu] → Detailed setup → Signal condition →

SP Setup →
→ SP H/L

Select

Select “High” or “Low”

3.4.2 External Temperature Fixation Mode

The external temperature can be fixed with this

mode. The parameter setting to enter the Fixation

Mode when the RTD sensor is disconnected is also

possible.

• Procedure to call up the display

[Root Menu] → Detailed setup → Signal condition →

ET Setup →
→ ET Fixed

Select “No”, “Yes” or “FALL BACK”

No: Shows process temperature

value

Yes: Fix the temperature value

FALL BACK: Fix the temperature

value when the RTD

sensor is disconnected.

→ Fixed ET

Val

Set the fixed temperature value

3.4.3 Integral Indicator Setup

The following displays are available for integral

indicator. A cycle can be shown by assigning

variables to the parameters at

Disp select.

• Input differential pressure

• Input static pressure

• Input external temperature

• User setting of Engineering Unit and Scale

• External input values and information (16 items)

F0305.ai

Available displays Description and related parameters

Input differential

pressure

(Pres)

Indicates values of input differential

pressure with the indication limits

–99999 to 99999.

PRES 45.6 kPa

Input static pressure

(SP)

Indicates values of input static

pressure with the indication limits

–99999 to 99999.

SP

6.178 MPa

Input ext. temperature

(ET)

Indicates values of input external

temperature with the indication limits

–99999 to 99999.

ET

22.95 degC

User setting of

Engineering Unit and

Scale

(Engr Disp)

Indicates values depending on the

engineering range (

Engr LRV and

Engr URV) with the unit (Engr Unit).

Engr LRV 0.0

Engr URV 45.0

Engr exp x100

Engr Unit m3/min

Engr point 1

External input value

and information1

Indicates 16 external input values

and information1. Information1 can

be used e.g. the kind of external

input value.

Disp User Value1: 6.178

Disp User Info1_1: FLOW

External input value

and information2

Indicates 16 external input values

and information2. Information2 can

be used e.g. the unit of external input

value. The external input value during

the information1 continues to display

during the information2 display.

Disp User Info1_2: g/s

P

SP

T

SP

SP

See (a) through (e) for the setting procedures.