4. Diagnostics

4.1 Self-Diagnostics

4.1.1 Identify Problems by Using the

Configuration Tool

The configuration tool can be used to run self-

diagnostics on a transmitter and check for incorrect

data settings.
The

Status menu is available for self-diagnostics.

If the specific diagnostic item is known for the

check, you can directly call up the item by using the

Status menu.
The status is categorized from 1 to 11.

See Table 4.1 to determine the status group.

Show an example below to confirm the status of

Status group 1.

Procedure to call up the Status display

[Root Menu] → Diag/Service → Status → Status group 1

If no error is detected, check mark is cleared on the

configuration tool.

If there is an error, “check mark” is displayed on the

configuration tool, and a countermeasure for that

error is necessary.

In addition to

Status group 1-11 parameters,

Status Bytes parameter in Address Map (Basic

Information) is available.

[Root Menu] →Diag/Service → Status

→ Status Bytes

Status information only mapped in

Address Map (Basic Information)

4.1.2 Checking with Integral Indicator

NOTE

If an error is detected by running self-diagnostics,

an error number is displayed on the integral

indicator. If there is more than one error, the error

number changes at three-second intervals.

See Table 4.1 regarding the alarm codes.

F0401.ai

Figure 4.1

Integral Indicator

4.1.3 Status Information

(1) Data quality and Limit status

EJX multivariable transmitter can handle

Device Variables (DP(Pres), SP, ET. Each

variable contains data quality and limit status

for providing useful status about the data value.

The data quality is normally “Good”. However,

in the case of a sensor failure or out of

measurement range, it turns to “Bad” or “Poor

Accuracy”. The limit status indicates whether

the data value is limited (i.e., not responding

to the process). When the limit status is

“Constant”, the value will not be changed. For

detail, refer to Table 4.1 and 4.2.

• Procedure to call up the display

[Device Variables]

[Root Menu] → Process variables → Device variables

and Status →
→ Press Data

Quality

Good, Poor Accuracy, Manual/

Fixed, or Bad is displayed.

→ press Limit

Status

Constant, Low Limit, High Limit, or

Not Limited is displayed.

It is the same about the SP and ET.

(2) Configuration Change Counter

The Configuration Change Counter is

incremented once for every user action

that changes the device’s configuration or

calibration. This value is never reset or written

and maintained even if power is removed from

the device.

• Procedure to call up the display

[Root Menu] → Diag/Service → Status →

→ Cfg chng

count

The configuration change times

are counted.

(3) Reset Configuration Change Counter

Configuration Change Counter can be reset by

this method.

• Procedure to call up the display

[Root Menu] → Diag/Service → Status → Reset Cfg

Chng Count