6 software write protection, 7 alarm, Software write protection -13 – Yokogawa EJX930A User Manual

Page 23: Alarm -13

Advertising
background image

<3. Parameter Setting>

3-13

IM 01C25R05-01EN

3.4.6 Software Write Protection

EJX multivariable transmitter configured data is

saved by using a write protection function. The

write protection status is set to “Yes” when 8

alphanumeric characters are entered in the

New

password field and transferred to the transmitter.
When write protection is set to ”Yes,” the transmitter

does not accept all the write possible parameters

changes. When the same eight alphanumeric string

entered in the

New password field is also entered

in the

Enable wrt 10min field and transferred to the

transmitter, it will be possible to change transmitter

parameters during a 10 minute period.
To change the transmitter from the write protection

”Yes” status back to write protection ”No” status,

use

Enable wrt 10min to first release the write

protection function and then enter eight spaces in

the

New password field.

• Procedure to call up the display

[Root Menu] → Detailed setup → Device information

→ Field device info → Wrt protect menu →
→ Write Protect

Display current protect mode

(Yes: protected, No: not protected)

→ Enable wrt 10

min

Release the protect function for 10

min.

→ New password Set the new password or change

the password

3.4.7 Alarm

The function is used to display the alarm codes

when the input differential pressure exceeds the

specified value within the calibration range. The

same is available for the input static pressure and

external temperature. Refer to Table 4.1 Alarm

Message Summary for the specific alarm code to

be generated.

(1) Alarm Setting
Select the process variable at

Process Alert which

the alarm is set, then set the alert mode for that

value.

• Procedure to call up the display

[Root Menu] → Detailed setup →Output condition →

Process Alerts →
Selection of

the process

variable for

alarm

→ Pres Alert Mode: Differential

pressure
→ SP Alert Mode: Static pressure
→ ET Alert Mode: External

temperature

Selection of

alert mode

Off: Disable the alert function
Hi Al Detect: High side alert detection
Lo Al Detect: Low side alert detection
Hi/Lo Al Detect: High and Low side

alert detection

(2) Threshold Level Setting
Set the threshold of high and low alert value for

alarm generation.

• Procedure to call up the display

[Root Menu] → Detailed setup →Output condition →

Process Alerts →

Parameter

Detail

→ Pres Hi Alert

Val

Set the threshold value of upper side

for differential pressure

→ Pres Lo Alert

Val

Set the threshold value of lower side

for differential pressure

→ SP Hi Alert

Val

Set the threshold value of upper side

for static pressure

→ SP Lo Alert

Val

Set the threshold value of lower side

for static pressure

→ ET Hi Alert

Val

Set the threshold value of upper side

for external temperature

→ ET Lo Alert

Val

Set the threshold value of lower side

for external temperature

Advertising