Yokogawa EJX930A User Manual

Page 20

Advertising
background image

<3. Parameter Setting>

3-10

IM 01C25R05-01EN

a. Display Selection

At

Disp select, select the variable that the

parameter Disp 1 will display on the integral

indicator.

• Procedure to call up the display

[Root Menu] → Detailed setup → Display condition →

Disp select →
→ Disp Out 1

Select desired display from five kinds

of displays shown above.

Set Disp OUT 2 to 16 in the same way if necessary.

“Not used” is also displayed as a selection item.
b. Cyclic Display
Displays can be displayed cyclically in the order of

the parameter number.
c. Display Resolution
User can change the position of decimal point

which is shown on the integral indicator.

• Procedure to call up the

Disp % reso display

[Root Menu] → Detailed setup → Display condition →

→ Disp %

Reso

Select the decimal point position of %

Normal: Display one digit below the

decimal point

High Resolution: Display two digits

below the decimal point

• Procedure to call up the

Pres disp point, SP

disp point and ET disp point display

[Root Menu] → Detailed setup → Display condition →

Disp Condition →
→ Pres disp

point

Select the decimal point position of

differential pressure (0, 1, 2, 3 or 4)

→ SP disp

point

Select the decimal point position of

static pressure (0, 1, 2, 3 or 4)

→ET disp point Select the decimal point position of

external temperature (0, 1, 2, 3 or 4)

d. User Setting of Engineering Unit and Scale
Engr disp range
parameters allow the engineering

unit and scale to be displayed. At

Set Engr Unit,

the following engineering units can be selected from

a list.

• Procedure to call up the display

[Root Menu] → Detailed setup → Display condition →

Engr disp range
→ Set Engr

Unit

Select the engineering unit

→ Engr LRV

Lower range value

→ Engr URV

Upper range value

→ Engr exp

Exponents for user scale display

→ Engr point

Decimal point position for user scale

display

→ Engr unit

Confirm and set unit

→ Engr Select Select the target of Engineering unit

Select the engineering unit from the list. Available

units are shown below

kPa

MPa

mbar

bar

psi

psia

mmH

2

O

mmHg

mmHgA

mmAq

mmWG

Torr

inH

2

O

inHg

inHgA

ftH

2

O

gf/cm

2

kgf/cm

2

kg/cm

2

G

kg/cm

2

A

atm

kg/h

t/h

m

3

/h

m

3

/min

l/h

l/min

kl/h

kl/min

Nl/h

Nl/min

Nm

3

/h

Nm

3

/min

ACFH

ACFM

CFH

SCFM

GPH

GPM

m

mm

in

ft

kg/m

3

g/cm

3

At

Engr Unit parameter, user can confirm and set

your own unit also.

Up to eight alphanumeric characters, spaces or one

slashe (/) can be input at

Engr Unit; only the first six

are displayed on the integral indicator.

• Procedure to call up the display

[Root Menu] → Detailed setup → Display condition →

Engr disp range →
→ Engr Unit

Set your own unit

Note that following symbols are not available:

# % & < > . * : + - , ’ ( )

The integral indicator shows “-- -- -- -- -- --” when

these symbols or more than two slashes are

entered.

e. External input values and information
16 external input values corresponds to

“Disp User

Value 1-16” selection lists and they can be selected

from 16 integral indicator display

“Disp Out 1-16”

parameters. Regarding the Procedure to call up the

display, refer to “a. Display Selection”.

External input value can be set to floating variable

parameter

“Disp User Value 1-16” parameters

and external input information1 can be set to 8

characters variable

“Disp User Info 1_1-16_1”

parameters.

External input information2 can be set into 8

characters variable

“Disp User Info 1_2-16_2.”

User can change the position of decimal point

which is shown on the integral indicator by

“Disp

User Value Point 1-16” parameters.

Advertising
This manual is related to the following products: