<3. Parameter Setting>

3-15

IM 01C25R05-01EN

(2) Device Variable Simulation Function
Using the simulation function, the output signal can

be confirmed by setting any value and status to the

selected device variable.

Call up the parameter and follow the message

shown.

After completing the step 5, the simulation starts.

Integral indicator shows output and alarm (AL.91)

alternately.

• Procedure of device variable simulation

Step 1 Call up the

parameter

[Root Menu] → Diag/

Service → Test → Simulate

2

Selection of

Device Variable

Select one parameter from

the list below

Off

Pres

SP

ET

3

Setting of Value

Input the simulate value

4

Setting of Data

quality

Select one parameter from

the list below

Bad

Poor accuracy

Manual / Fixed

Good

5

Setting of Limit

status

Select one parameter from

the list below

Not limited

Low limited

High limited

Constant

NOTE

• All the simulations for differential pressure,

static pressure and external temperature,

are reflected to the output. Accordingly,

LCD display, and communication output are

directly corresponded to the simulate value.

The alarm output is also available according

to the simulate value.

• Damping is applicable for differential

pressure, static pressure, and external

temperature simulation.

(3) Squawk
This feature can be used to identify the

communicating transmitter by remotely causing

LCD to display the particular pattern as shown in

the Figure 3.3.

“SQUAWK” continues for approximately 10

seconds, then is released automatically.

• Procedure to call up the

Squawk display

[Root Menu] → Diag/Service → Test → Squawk

P

SP

T

F

F0307.ai

Figure 3.3

LCD display for Squawk