<4. Diagnostics>

4-4

IM 01C25R05-01EN

Integral

Indicator

DTM

display

Status

group

Cause

Countermeasure

Value and Status (Data Quality and Limit Status)

Differential

Pressure

(DP)

Static

Pressure

(SP)

External

Temperature

(ET)

DP %

SP %

ET %

AL.35

P. HI

P high

alarm

5

Input pressure

exceeds

specified

threshold.

Check input.

Value:

Measured value

Status:

Good and Not Limited

(0xC0)

Value:

Measured value

Status:

Good and Not Limited

(0xC0)

AL.36

P. LO

P low

alarm

AL.37

SP. HI

SP high

alarm

Input static

pressure

exceeds

specified

threshold.

AL.38

SP. LO

SP low

alarm

AL.43

ET. HI

ET high

alarm

8

Input external

temperature

exceeds

specified

threshold.

AL.44

ET. LO

ET low

alarm

AL.50

P. LRV

Illegal P

LRV

6

Specified value

is outside of

setting range.

Check settings

and change

them as

needed.

Value:

Measured value

Status:

Good and Not Limited

(0xC0)

Value:

Hold value

Status:

Bad and

Constant

(0x30)

Value:

Measured value

Status:

Good and Not Limited

(0xC0)

AL.51

P. URV

Illegal P

URV

AL.52

P. SPN

Illegal P

SPAN

AL.53

P. ADJ

P SPAN

trim err

Adjust settings

and change

them as

needed.

Value:

Measured

value

Status:

Poor

Accuracy

and Not

Limited

(0x40)

Value:

Measured value

Status:

Good and Not Limited

(0xC0)

Value:

Measured

value

Status:

Poor

Accuracy

and Not

Limited

(0x40)

Value:

Measured value

Status:

Good and Not Limited

(0xC0)

P ZERO

trim err

AL.54

SP. RNG

Illegal SP

LRV

Check settings

and change

them as

needed.

Value:

Measured value

Status:

Good and Not Limited

(0xC0)

Value:

Measured

value

Status:

Good

and Not

Limited

(0xC0)

Value:

Hold value

Status:

Bad and

Constant

(0x30)

Value:

Measured

value

Status:

Good

and Not

Limited

(0xC0)

Illegal SP

URV

Illegal SP

SPAN