<4. Diagnostics>

4-2

IM 01C25R05-01EN

4.2 Alarms and Countermeasures

Table 4.1

Alarm Message Summary

Integral

Indicator

DTM

display

Status

group

Cause

Countermeasure

Value and Status (Data Quality and Limit Status)

Differential

Pressure

(DP)

Static

Pressure

(SP)

External

Temperature

(ET)

DP %

SP %

ET %

AL.01

CAP.ERR

P sensor

error

1

Sensor problem. Replace

capsule if the

error recurs

after the

transmitter is

restarted.

Value: Hold value

Status: Bad and Constant

(0x30)

Value: Hold value

Status: Bad and Constant

(0x30)

CT sensor

error

Capsule

temperature

sensor problem.

Replace

capsule.

Value: Hold value

Status: Bad and Constant

(0x30)

Value: Hold value

Status: Bad and Constant

(0x30)

Cap

EEPROM

error

Capsule

EEPROM

problem.

Value: Hold value

Status: Bad and Constant

(0x30)

Value: Hold value

Status: Bad and Constant

(0x30)

AL.02

AMP.ERR

Amp

EEPROM

error

Amplifier

EEPROM

problem.

Replace

amplifier.

Value: Hold value

Status: Bad and Constant

(0x30)

Value: Hold value

Status: Bad and Constant

(0x30)

CPU board

error

2

Amplifier

problem.

Value: Hold value

Status: Bad and Constant

(0x30)

Value: Hold value

Status: Bad and Constant

(0x30)

ET module

Com error

4

Value: Hold value

Status: Bad and Constant

(0x30)

Value: Hold value

Status: Bad and Constant

(0x30)

ET module

error

Value: Hold value

Status: Bad and Constant

(0x30)

Value: Hold value

Status: Bad and Constant

(0x30)

AL.03

ET. ERR*

ET sensor

error

External

temperature

sensor

disconnection.

Check external

temperature

sensor.

Value: Hold value

Status: Bad and Constant

(0x30)

Value: Hold value

Status: Bad and Constant

(0x30)

*:

When ET is set as “Fixed” or “Fall back”, this alarm does not occur.