Outputs

Type:

Two open collector outputs suitable for driving DC
solenoids or external relays. The outputs provide high
and low flow alarms or pulse output and low flow
alarm.

Switching Power:

200mA. 30VDC maximum.

Saturation Voltage:

0.8VDC typical across the output in the "on" state.

Isolation:

Both outputs are separately opto-isolated.

Pulse Duration:

If CAL00 = 1 (scaled pulse output):

(for pulse output)

a. 1ms if output frequency > 50Hz,
b. 10ms if output frequency is 5 ... 50Hz,
c. 100ms if output frequency is < 5Hz.

Physical

Temperature:

Operating Temperature:

-20°C to 60°C.

Dimensions:

97mm (3.8") high x 150mm (5.9") wide x 41mm
(1.6") deep (cable glands not included).

Protection:

Sealed to Nema 4x or IP67 standards.

Cable Entry:

By cable glands.

Wall Mounting:

Universal Mounting Bracket supplied as standard.

Pipe Mounting:

A galvanised metal bracket is available which enables
the Model 202A to be attached to a 2" vertical or
horizontal pipe.

Panel Mounting:

Supplied with mounting brackets.
Terminals accessible from rear (Note that the panel
mount version is not watertight).
Cutout: 141mm (5.6") wide x 87mm (3.4") high.

Specification 9