Yokogawa 202 Field Mounting Rate Totalizer User Manual

Page 17

Advertising
background image

3.2.2 The Cutoff Point

Because many transducers do not always exactly transmit 4mA when they are at
zero rate, it is often necessary to define a rate below which no integration takes
place. This is termed the cutoff point and is programmed as a percentage of the
Span, S.

For example, if S = 2200 kg/min in a square law system, and the cutoff point is
set at 20.0%, the actual cutoff rate Rc can be determined as follows:

The cutoff rate is defined as:

Rc = 2200 A

At 20% cutoff,

Rc = 2200 x 0.2

= 440 kg/min

The value of A which would produce this cutoff is:

A = 0.04

(since

= 0.2)

0.04

and the input signal would be:

I = 16mA x 0.04 + 4mA

= 4.64mA

Programming 15