Yokogawa 202 Field Mounting Rate Totalizer User Manual

Page 13

Advertising
background image

3.1 PROGRAM STEPS

Step

Comment

CAL 00

Pulse Output

0 = No pulse output, low and high alarms
1 = Scaled pulse output and low alarm

CAL 01

Span - whole numbers.

CAL 02

Span - digits after the decimal point.

The Span is the number of units of measure per
timebase (eg. litres/sec, Gal/min). The Span can be
programmed in the range of 0.000001 - 999,999.

See section 3.2.

CAL 03

Cutoff Point.

This determines the cutoff point as a fraction of Span.
See section 3.2.2.

CAL 04

Decimal Point for Rate Display.

The flowrate can be displayed with 0, 1, 2 or 3 decimal
point places.

CAL 05

Timebase for Rate.

The Rate can be displayed in units per second, minute,
hour or day.

0 = second
1 = minute
2 = hour
3 = day.

See section 3.2.

Programming 11