3.5 EXAMPLE

A vortex flowmeter has a maximum output of 20.538 litres/min at 20mA. It is
required to display the flowrate in litres/min with 1 decimal point and the total in
litres with no decimals. High and low alarms are required at 18 l/m and 2 l/m
respectively. The instrument is then programmed as follows.

CAL00

0

No Pulse Output

CAL01

00020

Span (Whole Numbers)

CAL02

5380

Span (Decimals)

03

0.05

Cutoff Point as a fraction of Span

04

1

Rate decimal position

05

1

Timebase

06

01

Filter disabled

07

0

Total decimal position

08

0001

Total Conversion (set to 1.0000)

09

0000

Total Conversion (decimals)

10

00002

Low Alarm

11

0000

Low Alarm

12

00018

High Alarm

13

0000

High Alarm

14

0

Linear Input

15

xxxx Accumulated Totals

SOFT

202A1.11

Software Version

Programming 19