Yokogawa 202 Field Mounting Rate Totalizer User Manual

Page 15

Advertising
background image

Step

Comment

CAL 11

Low Alarm - digits after the decimal point.

CAL 10 & 11 program the flowrate below which the
low alarm relay will close. The value can be
programmed in the range 0 to 999,999.

CAL 12

High Alarm or Pulse Output Factor - whole numbers.

CAL 13

High Alarm or Pulse Output Factor - digits after the
decimal point.

CAL 12 & 13 program the flowrate above which the
high alarm relay will close. The value can be
programmed in the range 0 to 999,999.

If the pulse output is selected (see CAL 00), the value will
represent the total per pulse. eg. 5 litres per pulse.

CAL 14

Input Flow Relationship.

0 = Linear Input
1 = Square Root Input.

CAL 15

Accumulated Total Reset.

CAL 15 displays the accumulated total which can be
reset by pressing and holding the RESET key for about
5 seconds.

SOFT

Software Version.

Programming 13