32 Calibration
5.1 PROGRAMMING THE SETUP PARAMETERS
Step
Display
Description
Text
Ref
1
CAL
BATCH
OPTION
TEST
END
Select the Calibrate mode to setup program
parameters.
Select Batch to enter Batch Setup parameters.
Option (if installed).
Select the test mode to check input signals.
Exit to normal operation.
5.2
5.3
5.4
The following steps are displayed if CAL is selected.
2
RESTOT
Reset all totals to zero.
To reset all totals (resettable and accumulated)
press the BATCH SET key once.
3
SCALE
Scaling Factor.
Fact
Enter the Scaling factor (K-factor) of the
flowmeter.
3.3.1
4
F dPt
Number of decimal points with which the Rate
is to be displayed between 0 to 0.00000.
5
t.base
The Timebase with which the Rate is
calculated must be entered as:
60secs
hours
days
secs
units/min
units/hour
units/day
units/second
6
FILTER
The filter constant for filtering the rate display. 3.3.2
1
No filtering.
to
99
Very heavy filtering.