40 Input Circuits

Switch Settings

The following switch settings are recommended for different input signal types.

Input Signal Type

Input Terminals

Switch Settings

CH1

+

-

1

2

3

4

5

6

7

8

a. Logic Signal, CMOS,

Pulse

9

8

off off off off on off off off

b. Open Collector or

Reed switch

9

8

off off off off on off on off

c. Namur Proximity

(set DC out to 8 volts)

11

9

off off on on on off off off

d. Switch or Reed Switch

with debounce circuit
(200Hz max)

9

8

off off off off on off on on

e. Coil (20mV P-P

minimum)

9

8

off on off off off off off off

f. Coil (low impedance)

22mV pp minimum

9

8

on on off off off off off off

General Specification

Switching Threshold:

2.5 Volts (except for input type c, e and f)

Maximum Input Voltage:

50V peak

Input Impedance

Input type a:

100K

Input types b & d:

10K

Input type c:

1K

Input type e:

100K

Input type f:

2.4K