Specification – Yokogawa 414 Batch Controller User Manual

Page 8

Advertising
background image

6 Specification

2. SPECIFICATION

General

Display:

6 digit LCD. 0.7" (17.8mm) high digits.

Display Update Rate:

0.25 seconds.

Transducer Supply:

8-24VDC field adjustable.
50mA maximum.

Power Requirements:

11.5 to 28.5 volts DC.
130mA typical current (no options).
AC Mains: Set internally to 95 - 135 VAC or

190 - 260 VAC.

Operating Temperature:

0 to 55

°C standard.

Dimensions:

5.7" (144mm) wide x 2.8" (72mm) high x
7.0" (178mm) deep.

Cutout:

5.5" (139mm) wide x 2.6" (67mm) high.

Frequency Input

Frequency Range:

Minimum:

0.25Hz on Rate.
0Hz on Total.

Maximum: 10KHz.

Input Circuits:

See Sections 6.1 and 6.2.

Scaling Range:

0.1000 to 50,000.

Relay Outputs

Maximum Switching Power:

1250VA.

Maximum Switching Voltage: 250VAC, 30VDC.
Maximum Switching Current: 5 Amps.