34 Calibration

5.2 ENTERING THE BATCH PARAMETERS

Step

Display

Description

Text

Ref

1

BATCH
OPTION
TEST
END
CAL

Enter Batch Parameters.
Option (if installed)
Check Input Signals.
Exit to normal operation.
Program Setup Parameters.

5.3
5.4

5.1

The following steps are displayed if BATCH is selected.

2

BATCH L
xxxxxx

Maximum Batch Size which can be entered.
Set to 0 if no limit on batch size.

3.2

3

AUTO S

Off
On
xx:xx

Automatic restart feature.

Disable.
Enable.
If enabled, automatically restarts the batch
xx:xx (mins:sec) after the end of the last batch.

3.2.4

4

START. T

xx:xx

Slow start time.

Time, in (minutes:seconds), when Relay 2 will
energise once the batch has started.

3.2

5

PREST

xxxx

Prestop Quantity.

Quantity at which Relay 2 will de-energise
before the end of the batch. (eg. If the batch
quantity is 100 litres and Prest is 2 litres, relay
2 will de-energise after 98 litres.)

3.2