Yokogawa 212 Heat Calculator User Manual

Page 22

Advertising
background image

Parameter

Value

Description

6. OFFSET

x.x
YES

0.0
NO

The offset between temperature sensors
(see Section 3.5).

The offset function is disabled.

7. FM

LOC

Feed
Ret

Location of the flowmeter in either the
feed or return line.

If High and Low alarms are installed

8. REL0

Flw

H

Flw L
Pwr H
Pwr L

t° H

t° L

Ft° H
Ft° L
Rt° H
Rt° L

Defines the parameter for Relay 0 output
as being high or low alarm for flow,
power, temperature difference, feed or
return temperatures.

9. REL0

xxxx.xxx

Set point for parameters set in step 8
above. For low alarms the relay will
close if the parameter is below the set
point. For high alarms it will close if the
parameter is above the set point.

10

REL1

...

Defines the parameter for Relay 1 as in
step 8 above.

11.

REL1

xxxx.xxx

Set point for parameter for Relay 1 as in
step 9 above.

20 Operation

Advertising