Yokogawa 212 Heat Calculator User Manual

Page 50

Advertising
background image

Parameter

Value

Description

25. Df

DIS

YES

NO

Display will revert to Energy Total if no
key has been pressed for 10 seconds.

Display will stay on the last displayed
parameter.

26. Fr

RES

YES
NO

Enable RESET key on front panel.
Disable RESET key.

27.

PK/OPK

OFF
ON

Selects whether Energy will be totalised
in separate Peak and Off-Peak registers.
If set to OFF, Set-up continues at step
30.

28. PK

ON

xx
hour

Sets the hour at which energy totalisation
will commence in the PEAK register.
(Only available if mode is set to Heat,
Cool or Heating/Cooling.)

29. PK

OFF

xx
hour

Sets the hour at which energy totalisation
will commence in the OFF PEAK
register. (Only available if mode is set to
Heat, Cool or Heating/Cooling.)

30. LOG

OFF
MONTH
WEEK
DAY
HOUR

Selects the interval at which Logging
will take place.

Logging is only available if the mode
(step 2) is set to Heating, Cooling or
Heating/Cooling and the Peak/Off-Peak
(step 27) is set to OFF. If logging is not
available, this step will not be displayed.

48 Set-up Mode