4.3.4 Function Codes
The Model 212 accepts the following function codes:
Code
Name
Description
03
Read data register(s)
Obtain the content of one or
more 2 byte data registers.
06
Preset data register
Preset one 2 byte data register.
07
Read status register
Obtain the content of 1 byte
status register.
16
Preset data register(s)
Preset one or more 2 byte data
registers.
4.3.5 Exception Response
The Model 212 forms an exception response by adding 80H to the function code
and using an exception code as the 1 byte data field in the returned frame.
Implemented exception codes are as follows:
Code
Name
Description
01
Illegal function
The function code is not a
legal action for the slave.
02
Illegal data address
The data address is not a legal
address for the slave.
03
Illegal data value
The data value is not a legal
value for the slave.
Communications 37