4.3.4 Function Codes

The Model 212 accepts the following function codes:

Code

Name

Description

03

Read data register(s)

Obtain the content of one or

more 2 byte data registers.

06

Preset data register

Preset one 2 byte data register.

07

Read status register

Obtain the content of 1 byte
status register.

16

Preset data register(s)

Preset one or more 2 byte data

registers.

4.3.5 Exception Response

The Model 212 forms an exception response by adding 80H to the function code
and using an exception code as the 1 byte data field in the returned frame.
Implemented exception codes are as follows:

Code

Name

Description

01

Illegal function

The function code is not a

legal action for the slave.

02

Illegal data address

The data address is not a legal

address for the slave.

03

Illegal data value

The data value is not a legal

value for the slave.

Communications 37

Advertising