Code

Name

Description

05 Acknowledge

The slave has accepted the
request and is processing it,
but a long duration of time will
be required to do so.

06

Slave device busy

The slave is engaged in
processing a long duration
program command. The
master should re-transmit the
message later when the slave is
free.

4.3.6 List of Data Registers

The following list describes addresses and meaning of data registers for the
Model 212. Engineering units programmed during setup are used for floating
point values. Conventional numbering of registers often starts from 1, therefore
be aware that "register 1" in this case has an "address 0" and so on.

Read and Write Registers

Address

Name

Value Note

00

Heating mode

00 - heat
01 - cool
02 - heat/cool
03 - charge/discharge

01

Total reset

00 - no action
01 - reset totals

02

Flowmeter location

00 - feed line
01 - return line

38 Communications