<5. CONFIGURATION>

5-9

IM 11M12D01-61E

Table 5.8 Parameters for Trend Objects

Ten trend objects are not factory-set.

Table 5.9 Trend Objects

Figure 5.5 Example of Configuration

T0509.ai

Index

Parameter

Factory Setting

32000 to

32007
32008

32009

TREND_DIS.1

TREND_DIS.2

TREND_FLT.1 to

TREND_FLT.8

Not set.

Not set (these parameters

are used with a DI block).

F0505.ai

AI2 OUT

AI1 OUT

FBOD

Alert

Trend

VCR

DLSAP

DLCEP

Fieldbus Cable

AV550G

0xF8 0xF3 0xF4 0xF7 0xF9 0x20

0x07

#1 #2 #3 #4 #8 #6

#7 #5

#1

#3

#2

DI2

OUT

DI1

OUT

System

Management

Information

Base (SMIB)
Network

Management

Information

Base (NMIB)

Resource

block

Transducer

block

Link object

Host 1

Host 2

Device

Sub-

index

Parameters

Description

1

Block Index

Specifies index of head of function block that is creating the trend.

2

Parameter Relative

Index

Specifies index of parameter used for trend, relative to head of function

block. In the AV550G, the following three types of trends are possible.

7: PV

8: OUT

19: FIELD_VAL

T0508.ai

3

Sample Type

Specifies how trends are taken.

Choose one of the following 2 types:

1: Sampled upon execution of a function block.

2: The average value is sampled.

4

Sample Interval

Specifies sampling intervals in units of 1/32 ms.

Set the integer multiple of the function block execution cycle.

5

Last Update

The last sampling time.

6 to 21 List of Status

Status part of a sampled parameter.

21 to 37 List of Samples

Data part of a sampled parameter.