Mao function block parameters -21, 7 mai function block parameters, 8 mao function block parameters – Yokogawa Multi Channel Oxygen Analyzer System ZR22/AV550G User Manual

Page 40

Advertising
background image

<5. CONFIGURATION>

5-21

IM 11M12D01-61E

Table 5.18 Alarm Priority

DISC_LIM

Sets the value of the Discrete Alarm corresponding to block output OUT_D.

When the value of OUT_D is the same as this value, an alarm is output.

5.6.7 MAI Function Block Parameters

The MAI function block parameters can be read from the host and set. Here we explain the more

important parameters.
MODE_BLK

Three block modes O/S, Auto, and Manual are supported. In O/S (Out of Service) mode the MAI

function block does not operate. In Manual mode the value is not updated. In Auto mode the

measured value is periodically updated. The factory default mode setting for all MAI blocks is O/S.
CHANNEL

This is a value from the transducer block that is connected to the MAI block input.

For the AV550G, it’s set to 6.

5.6.8 MAO Function Block Parameters

MODE_BLK

Four block modes O/S, Auto, Manual, and Local Override are supported. In O/S (Out of Service)

mode the MAO function block does not operate. In Manual mode the value is not updated. In Auto

mode the measured value is periodically updated. In Local Override mode, can be set in actual.

The factory default mode setting for MAO blocks is O/S.
CHANNEL

This is a value from the transducer block that is connected to the MAI block input.

For the AV550G, it’s set to 7.
MO_OPTS

Specifies whether FSTATE_VAL is used or not. 2- byte bit array.

Value

Descriptions

0

Alert output suppressed, and alarm parameters not updated.

1

Alert output suppressed.

3 to 7 Advisory alarm.

8 to 15 Critical alarm.

T0518-1.ai

T0518-2

Bit

Label

Description

0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

Fault state to value 1
Fault state to value 2
Fault state to value 3
Fault state to value 4
Fault state to value 5
Fault state to value 6
Fault state to value 7
Fault state to value 8

In Fault State, write FSTATE_VAL1 to IN_1
In Fault State, write FSTATE_VAL2 to IN_2
In Fault State, write FSTATE_VAL3 to IN_3
In Fault State, write FSTATE_VAL4 to IN_4
In Fault State, write FSTATE_VAL5 to IN_5
In Fault State, write FSTATE_VAL6 to IN_6
In Fault State, write FSTATE_VAL7 to IN_7
In Fault State, write FSTATE_VAL8 to IN_8

Use fault state to value on restart1
Use fault state to value on restart2
Use fault state to value on restart3
Use fault state to value on restart4
Use fault state to value on restart5
Use fault state to value on restart6
Use fault state to value on restart7
Use fault state to value on restart8

On restart, write FSTATE_VAL1 to IN_1
On restart, write FSTATE_VAL2 to IN_2
On restart, write FSTATE_VAL3 to IN_3
On restart, write FSTATE_VAL4 to IN_4
On restart, write FSTATE_VAL5 to IN_5
On restart, write FSTATE_VAL6 to IN_6
On restart, write FSTATE_VAL7 to IN_7
On restart, write FSTATE_VAL8 to IN_8

Advertising