Functions, 1 i/o card, Functions -1 – Yokogawa GC1000 Mark II Process Gas Chromatograph User Manual

Page 10: I/o card -1

Advertising
background image

<3. Functions>

3-1

IM 11B06F01-01E

3. Functions

ASIU has the following functions.

1. Access the I/O cards (DI read, DO write and read back, AI read)
2. Creating the alarm information
3. Interface to DCS through Modbus RTU Slave or Modbus TCP Server

3.1

I/O card

ASIU accesses the I/O card such as DI, DO and AI attached on the FCN to read and write the

data periodically.
Scan interval: 100 msec.
The slots which is not assign the I/O on the resource configurator are not made a read and write,

even IOP check.

l

DI card

Max. 16 points of the digital inputs are read periodically.

l

DO card

Max. 16 points of the digital output are written and read back the output status periodically.

l

AI card

Max. 16 points of the analog data is read periodically.
Data type: Real number
Range:

0.0 to 1.0

Accuracy: It follows the specification of each module used. Refer to the GS of the relevant ana-

log card.

Input signal

AI

IOP

106.3 % or more

1.0

1

100 to 106.3 %

1.0

0

0 to 100 %

0.0 to 1.0

0

-6.3 to 0 %

0.0

0

-6.3 % or less

0.0

1

The value of the analog data which is not assigned on the resource configurator is always 0, and

the IOP is also 0.