Operation for Display of Measurement Items and Measurement Method

4-9

IM 77C01E01-01E

1

2

3

4

5

A

4.5

Displaying Energy Values

Optional Integrating Function

The optional integrating function integrates the active power while the control signal for optional
integration is activated (ON for activating and OFF for deactivating). The operation for this signal can be
performed via communication or by digital input.

NOTE

The control signal for optional integration of the PR300 with the demand measuring function can be

controlled only via communication. It is not possible by digital input.

The active power below the integrated low-cut power cannot be integrated.

Once the control signal for optional integration is controlled via communication, communication is

the only means for controlling that signal until system reset* is performed. The same applies to
control by digital input.
* System reset can be performed by turning off/on the power supply for the PR300 or by executing

remote reset via communication.

When the system is reset, the optional integrated value is reset to 0.

If power failure occurs during integration, an optional integrated value is reset to 0.

Example operation of the control signal for optional integration via communication

Digital input
ON

Digital input
OFF

Start
command

Stop
command

Data update

Time

The active power during this time period is integrated.

These control
signals are invalid.

Example operation of the control signal for optional integration by digital input

Start
command

Digital input
ON

Digital input

OFF

The active power during this time period is integrated.

Stop
command

Data update

These control
signals are invalid.

Time

Digital input

Number of inputs:

1

Input signal:

ON signal 4.5 to 25 V DC, OFF signal within

Ϯ1 V DC

Maximum integrated value

99999 Wh (After the integrated value reaches this maximum value, it returns to “0.”)

Data update

When the control signal for optional integration is turned off and then turned on:

The displayed measured value is reset to 0, and integration starts. The integrated value before
resetting (previous value) can be confirmed via communication.

When the control signal for optional integration is turned on for a while and turned off later:

The displayed measured value is the integrated value. This value display is retained until the control
signal for optional integration is turned on again.