A-6

IM 77C01E01-01E

Appendix 1 Specifications of PR300

Modbus/TCP function

Code

03

06

08

16

Function

Reads data from multiple D registers

Writes data into D register

Performs loopback test

Writes data into multiple D registers

Description

Capable of reading data from up to 64 registers continuously.

Capable of writing data into one resiter.

Capable of performing a communication test.

Capable of writing data into up to 32 registers continuously.

Overview of Modbus/TCP protocol

PDU

The Simple Protocol Data Unit (PDU) is the same as
Modbus/RTU (Modbus protocol via serial communication).

MBAP Header

Function code

Data

The structure of the Modbus/TCP protocol is as follows:

Byte No

Description

0

Transaction ID

1

2

Protocol ID

3

4

Number of bytes

5

6

Unit ID

The Modbus Application Protocol Header (MBAP Header) is made of the
following seven bytes:

Ethernet - Serial gateway function
Equipped with an Ethernet communication connector and an RS-485 communication terminal, the
PR300 receives a Modbus/TCP command from Ethernet and relays it to the RS-485 communication
terminal. The PR300 allows connection to RS-485 serial communication devices (Modbus/RTU
protocol) via the network.

Higher-level device
IP address [192.168.1.1]
(arbitrary)

Ethernet

10BASE-T/100BASE-TX

Station number 01 (fixed)
IP address [192.168.1.2] (arbitrary)

PR300 (with Ethernet
communication function)

RS-485 connection

Station number 02
(arbitrary)

Station number 10
(arbitrary)

RS-485 serial communication device
Power monitor of POWERCERT Series
Digital indicating controller of GREEN Series
Signal conditioner of JUXTA Series

(Example)

RS-485 communication

Protocol

Baud rate

Parity

Stop bit

Data length

Modbus/RTU

9600bps

None, even, odd

1 bit

8 bits

(Note)

If Ethernet communication is used, the RS-485 communication interface is
used specifically for the Ethernet-serial gateway function. Therefore, it is not
possible for a higher-level device such as a PC to access the PR300 via the
RS-485 communication interface.

Standard Performance

Accuracy rating

Active energy/optional active energy (Wh)

Ϯ0.5% (EN60687 accuracy: Class 0.5 or equivalent)

Active power (W)

Ϯ0.5% of F.S.

Voltage (V)

Ϯ0.25% of F.S. (voltage rms)

Current (A)

Ϯ0.25% of F.S. (current rms)

Frequency (Hz)

Ϯ0.5Hz

Demand

Ϯ0.5%

Calculation accuracy The value is calculated to

Ϯ1 digit from the measured value for reactive energy, apparent

energy, reactive power, apparent power, power factor, or current.*
* Current is only for the 2.5-element measurement.

Backup upon power failure

The last integrated values obtained immediately before the power failure are held for active
energy, regenerative energy, reactive energy, and apparent energy.