4.7 Demand Measurement (Optional Measuring

Function)

The PR300 (with the demand measuring function) can measure the average power or current during the
set demand period.
This section explains the example display of measured value, measuring range, measurement operation,
and example measurement. For setting conditions related to the demand measurement such as demand
period, refer to Section 3.8, “Setting Demand Measurement Conditions.”

Example Demand Display and Measuring Ranges

Demand power

Start/stop of
demand
measurement
and alarm release

Turns on during
demand
measurement

Turns on during demand alarm

Turns on during demand measurement

Turns on while the
maximum value is displayed

Demand power

Supplementary
unit
(refer to the
table on the right)

Secondary rated power

ϫ

1.2

ϫ

VT ratio

ϫ

CT ratio

6 W to less than 100 W

100 W to less than 1 kW

1 kW to less than 10 kW

10 kW to less than 100 kW

100 kW to less than 1 MW

1 MW to less than 10 MW

10 MW to less than 100 MW

100 MW to less than 1 GW

1 GW or greater

Measuring range

0.00 to 99.99 W

0.0 to 999.9 W

0 to 9999 W

0.00 to 99.99 kW

0.0 to 999.9 kW

0 to 9999 kW

0.00 to 99.99 MW

0.0 to 999.9 MW

0 to 9999 MW

Demand current

Start/stop of
demand
measurement
and alarm release

Turns on during
demand
measurement

Turns on during demand alarm

Turns on during demand measurement

Turns on while the
maximum value is displayed

Demand current

Supplementary
unit
(refer to the
table on the right)

Current range

ϫ

1.2

ϫ

CT ratio

0.06 A to less than 10 A

10 A to less than 100 A

100 A to less than 1 kA

1 kA to less than 10 kA

10 kA to less than 100 kA

100 kA to less than 1 MA

Measuring range

0.000 to 9.999 A

0.00 to 99.99 A

0.0 to 999.9 A

0 to 9999 A

0.00 to 99.99 kA

0.0 to 999.9 kA

The phase of the demand current
being measured can be switched for display.

Phase indication lamp

Demand Measurement Procedure

Equation:

(Pt - Ps)

ϫ (60 minutes ϫ 60 seconds Ϭ t)

Pt:

Current integrated value

Ps:

Integrated value at the beginning of the demand period

t:

Demand elapsed time (data update period: 10 seconds)

Start demand
measurement

Stop demand
measurement

Demand

period

Average
power
(current)
update

Demand measuring time (while the maximum demand value is retained)

Average
power
(current)
update