Chapter 5 troubleshooting, 1 error display and recommended response, Error display and recommended response – Yokogawa PR300 Power and Energy Meter User Manual

Page 56: Chapter 5, Troubleshooting, Error display and recommended response -1, Errors during operation, Errors at the measured input error, Errors at the time of setting parameters

Advertising
background image

Troubleshooting

5-1

IM 77C01E01-01E

1

2

3

4

5

A

5.1

Error Display and Recommended Response

Failure at the Time of Turning on the Power and during Operation

Recommended

response

Request
repair.

Upper display

of measured

value display

Error display

Status

Power

lamp

Phase and

wire system

lamp

Communi

-cation

lamp

Pulse

lamp

Unstable

Off

Off

Off

Normal

action

Normal

action

Communi-

cation

Disabled Disabled Disabled Disabled

Off

Power

calculation

Disabled

Pulse output

(contact

point)

Analog

output

Demand

alarm

Type of fault

RAM error

ROM error

System data
fault

Calibration
data fault

Parameter
fault

Backup fault

Normal

action

Off

Normal

action

Normal

action

Disabled

Normal

action

Disabled

Disabled

Disabled

Normal

action

Normal

action

EEPROM
error

ADC error

Errors during Operation

Recommended

response

Confirm the
input.

The product is

restored when

a normal frame

is received.

Upper display

of measured

value display

Error display

Status

Power

lamp

Phase and

wire system

lamp

Communi

-cation

lamp

Pulse

lamp

On

Blinks at
intervals of
125
milliseconds.

Normal

action

Normal

action

Normal

action

Normal

action

Normal

action

Normal

action

Normal

action

Normal

action

Communi-

cation

Power

calculation

Pulse output

(contact

point)

Analog

output

Demand

alarm

Type of fault

Measured
input error

Communication
error

blinking

Normal
action

Errors at the Measured input error

Measurment items

Active power

Reactive power

Apparent power

Voltage

Current

Power factor

Frequency

Measured input error conditions

120% or more of “secondary rated
power

ϫ VT ratio ϫ CT ratio”

120% or more of
“voltage range

ϫ VT ratio”

Less than 10% of
“voltage range

ϫ VT ratio”

120% or more of
“current range

ϫ CT ratio”

Out of the measuring range
(LEAD 0.5 to 1 to LAG 0.5)

Out of the measuring range (45 to 65 Hz)

Error display

and the measured value

blink alternately

Recommended response

The error is cleared by inputting a
measured value less than 120%.

The error is cleared by inputting a
measured value less than 120%.

The error is cleared by inputting a
measured value within the
measuring range.

The error is cleared by inputting a
measured value 10% or more.

Errors at the Time of Setting Parameters

Example

The setpoint is out of the range.

Error display

and the setpoint blink alternately on

the display.

Recommended response

The error is cleared by setting a value
within the range.

Chapter 5

Troubleshooting