You can calculate your power requirements by combining the power draws for the various blades and
fan units in your configuration. While you may use fewer ports in a given blade, it is always safer to
use the power requirement of a fully populated blade.

Power demands per component

TABLE 23

Blade or fan
units

Maximum Power
Draw (Watts)

Type of Blade Ports per blade

Number of
blades
permitted in
chassis

Total ports per
chassis

CP8

40

Control blade

NA

2

NA

CR16-8

240

Core blade

16 64-Gbps QSFP
ports

2

32 quad ports
(128 ports)

FC8-32E

140

Port blade

32 8-Gbps SFP+

up to 8

256

FC8-48E

160.4

Port blade

48 8-Gbps SFP+

up to 8

384

FC8-64

126.4

Port blade

64 8-Gbps SFP+

up to 8

512

FC16-32

140

Port blade

32 16-Gbps SFP+
- can use 8-Gbps
SFP+

up to 8

256

FC16-48

160.4

Port blade

48 16-Gbps SFP+
- can use 8-Gbps
SFP+

up to 8

384

FC16-64

134

Port blade

16 QSFPs (4 16-
Gbps ports per
QSFP)

up to 8

512

FCOE10-24

250

Application
blade

24 10-Gbps SFP+
Fibre Channel
over Ethernet

up to 1 (slot 1
only)

24

FS8-18

235

Encryption
blade

16 8-Gbps SFP+

up to 4

64

FX8-24

250

Extension
blade

12 8-Gbps SFP+,
10 1-Gbps
Ethernet, 2 10-
Gbps Ethernet

up to 4

48 8-Gbps, 40 1-
Gbps Ethernet, 8
10-Gbps
Ethernet

Fan unit

90

NA

NA

3 fans per
chassis

NA

Power supply redundancy is key to your installation, so any demand must be met with twice the
capacity. Refer to the following table for power supply requirements for specific demand ranges.

Specifications