Determining the status of a power supply – Brocade DCX 8510-8 Backbone Hardware Reference Manual User Manual

Page 67

Advertising
background image

CR blade LED descriptions

TABLE 6

LED purpose

Color

Status

Recommended action

Power

Steady green

CR16-8 blade is on.

No action required.

No light (LED is
off)

CR16-8 blade is not on.

Ensure that the blade is firmly
seated and has power.

Status

No light (LED is
off)

CR16-8 blade is either healthy
or does not have power.

Verify that the power LED is on.

Steady amber

CR16-8 blade is faulty or the
switch is still booting.

Ensure that the blade is firmly
seated and the switch has
completed booting. If the LED
remains amber, consult the Brocade
DCX 8510-8 supplier.

Slow-flashing
amber (on 2
seconds, then off
2 seconds)

CR16-8 blade is not seated
correctly or is faulty.

Pull the blade out and reseat it. If the
LED continues to flash, replace the
blade.

Fast-flashing
amber (on 1/2
second, then off
1/2 second)

Environmental range
exceeded.

Check for out-of-bounds
environmental condition and correct
it.

QSFP connector
status LED

No light (LED is
off)

No QSFP module, all four
QSFP ports are disabled

No action needed if the QSFP is not
installed or verify that the QSFP is
fully inserted.

Steady amber

QSFP module is in, all four
ports have no signal/no sync.

Ensure that the cable is properly
connected. If the LED remains
amber, consult the Brocade DCX
8510-8 supplier.

Blinking amber

Port is disabled or faulted, FC
link activity, segmented,
loopback mode, also during
transition between cable plug
in and all four ports online.

Check for console messages or wait
for all four ports to come online.

Steady green

QSFP module is in and all
ports are online.

No action needed.

Refer to

Port Numbering Template

on page 151 for a map of the ports and a table of external ports

to internal ports as shown in the slotShow command.

Determining the status of a power supply

Complete the following steps to determine the status of a power supply.

Determining the status of a power supply

Brocade DCX 8510-8 Backbone Hardware Reference Manual

67

53-1002180-07

Advertising