15 limit switch (sp1), 16 operating hours – LumaSense Technologies IGA 320/23-LO User Manual

Page 23

Advertising
background image

IGA 320/23-LO Operating Manual

Settings / parameter descriptions 23

4.15 Limit switch (SP1)

The pyrometer is equipped with a switch contact (opto relays; max. 50 V DC, 0.2 A; max. power
300 mW), controlled from the measuring signal. The contact is activated with:
Close above: The contact closes (switches to ground), if the temperature entered in the SP1

box is exceeded. If the temperature falls below that value minus the hysteresis the contact opens
(a hysteresis between 2 and 20 °C can be set to avoid oscillating of the switch in the switch

point).
Close below: The contact closes (switches to ground), if the temperature falls below the
entered value in the SP1 box. If the temperature exceeds that value plus the hysteresis the
contact opens (a hysteresis between 2 and 20 °C can be set to avoid oscillating of the switch in

the switch point).

4.16 Operating hours

Shows the operation time that the pyrometer has been in use.