6.4 DRYER CONTROLS

The control is housed in a NEMA 4X enclosure and it has the following

features:

- Power switch

- Power On light

- Fail to Switch light

- Alarm Reset pushbutton

- Hour Meter

See

Figure 6B for control box door.

6.4-2 SWITCHING FAILURE:

When there is a switching failure (failure of control solenoid valves

SV1 & SV2; failure of exhaust valve to open; or clogging of exhaust

muffler), the Fail to Switch LED will be lit. This will energize the

Alarm Contacts shown in

FIGURE 10D. The contacts can be wired

for remote annunciation. To reset the Switching Failure Alarm press

the Alarm Reset Pushbutton on the front of the control box. If the

condition causing the alarm is not corrected, the alarm will

re-activate in 90 seconds.

6.3 MOISTURE INDICATOR

The moisture indicator is in the center of the panel. The moisture

indicator is a clear plastic tube filled with moisture sensing crystals. A

sample of outlet air is directed through the indicator.

The crystals will change colors from

PINK (indicating wet air) to

BLUE (indicating dry air) as the dew point of the air changes from

+20

O

F to -40

O

F.

OPERATION

SECTION 6

FIGURE 6A PNEUMATIC SCHEMATIC

6.4-1 SMART RELAY:

The dryer cycle is controlled by a SmartRelay, two solenoid valves

and two pressure switches. The dryer timing chart is shown in

FIGURE 6C. The SmartRelay has a battery back-up that will hold

the program in memory safely for 2 years.

6.4-3 HOUR METER:

The Hour Meter is located on the front of the control box. It is used

to log the total number of hours that the Prep-40 dryer system has

been in operation.