Configuration table – GW Instek PSU-Series Programming User Manual User Manual
Page 25

GETTING STARTED
25
Configuration Table
Please use the configuration settings listed below when applying
the configuration settings.
Normal Function
Settings
Setting Setting Range
Output ON delay time
F-01
0.00s~99.99s
Output OFF delay time F-02
0.00s~99.99s
V-I mode slew rate select F-03
0 = CV high speed priority (CVHS)
1 = CC high speed priority (CCHS)
2 = CV slew rate priority (CVLS)
3 = CC slew rate priority (CVLS)
Rising voltage slew rate F-04
0.001~0.06V/msec (PSU 6-200)
0.001~0.125V/msec (PSU 12.5-120)
0.001~0.2V/msec (PSU 20-76)
0.001~0.4V/msec (PSU 40-38)
0.001~0.6V/msec (PSU 60-25)
Falling voltage slew rate F-05
0.001~0.06V/msec (PSU 6-200)
0.001~0.125V/msec (PSU 12.5-120)
0.001~0.2V/msec (PSU 20-76)
0.001~0.4V/msec (PSU 40-38)
0.001~0.6V/msec (PSU 60-25)
Rising current slew rate F-06
0.001~2A/msec (PSU 6-200)
0.001~1.2A/msec (PSU 12.5-120)
0.001~0.76A/msec (PSU 20-76)
0.001~0.38A/msec (PSU 40-38)
0.001~0.25A/msec (PSU 60-25)
Falling current slew rate F-07
0.001~2A/msec (PSU 6-200)
0.001~1.2A/msec (PSU 12.5-120)
0.001~0.76A/msec (PSU 20-76)
0.001~0.38A/msec (PSU 40-38)
0.001~0.25A/msec (PSU 60-25)