HT instruments PQA824 User Manual

Page 132

Advertising
background image

PQA400 - PQA823 - PQA824

EN - 131

10.3. INRUSH CURRENTS (ONLY PQA82X)
The PQA82x meters permits the real time detection of inrush current events, typical of
start-up of electrical machines and also for other industrial applications (e.g.
troubleshooting problem regarding loads switching, correct calculation of protection
devices, oscillating currents, etc…) as shown in the following pictures:

Fig. 208: Parameters of standard inrush current event

Fig. 209: Parameters of oscillating inrush current event

The meter detect and recording as inrush current all the events where the phase currents
TRMS values are over a set limit threshold. The maximum number of recorded events is
fixed to 1000.
During setting operation before recording start the user can be modify the below
parameters:

Current limit threshold:

Current value of detection and recording of the event.
The maximum set value of this parameter is always
equal to the full scale of used transducer clamps.

Advertising
This manual is related to the following products: