HT instruments PQA824 User Manual

Page 63

Advertising
background image

PQA400 - PQA823 - PQA824

EN - 62

VOLTAGE ANOMALIES

GENERAL MENU

PARAMETER

SETTINGS

SYSTEM

Analyzer Settings

System

Not modified

Each system

Freq[Hz]

Clamp Type

FS Clamp[A]

VT Ratio

Analyzer Settings - Advanced

Zoom Graphics

Harm. Type

Harm. Values

Zoom 1st Harm.

Average Values

Recording Settings

Comments VOLTAGE

ANOMALIES

Each system

Start Not

modified

Stop Not

modified

Integration period

1min

Cogeneration OFF

General Parameters

V1N, VN-PE, Hz

Single phase

V12, V23, V31, Hz

3-wire, ARON

V1N, V2N, V3N, VN-PE,

Average (if activated), Hz

4-wire

Voltage harmonics

OFF

Each system

Current harmonics

OFF

Voltage anomalies

ON

Ref. Voltage anomalies

230V Single,

4-wire

400V 3-wire,

ARON

Up threshold anomalies

+6%

Each system

Low threshold anomalies

-10%

Inrush current (only

PQA82x)

OFF

Flicker OFF

Unbalance

Not available

Single phase

ON 3/4-wire,

ARON

Spike (only PQA824)

ON (150V)

Each system

Table 8: Selected parameters of VOLTAGE ANOMALIES configuration