5.4.3. Start

and

Stop

These items permits to define the method to enable and disable the recordings with meter
(see § 5.4.13). The possible options are:

Manu: Each recording is enabled/disabled in MANUAL mode by pressing GO/STOP

key.

Auto: Each recording is enabled/disabled in AUTOMATIC mode, starting from a setting

and valid date/hour by preliminary pressing of GO/STOP key.

The default configuration is always the MANUAL mode and the flags of these s are not
disable. To change from MANUAL mode to AUTO mode (see § 5.4.13.1) performs the
below steps:

1. Move the cursor using arrows keys on the field relative to “Start:Manu” or

Stop:Manu”, marked with blue background.

2. Press F4 key (alternatively touch the MODIFY at display). In the bottom of display a

command bar with “Manu” is shown.

3. Press F3 key (MOD(+)) or F4(MOD(-)) and select “Auto” .
4. Use left or right arrows keys to moving on date and hour fields. Using the up arrow key

or F3 (MOD(+)) key to increase the value and the down arrow key or F4 (MOD(-)) key
to decrease the value.

5. Press SAVE or ENTER keys (or the smart icon

) to save the settings. The Automatic

mode and the set date/hour are shown at display.


5.4.4. Integration

period

This option permits to set the integration period (see § 10.8.1) which is the time interval
between two sequential recordings within the global duration of measurements. The flag of
this option is always active and not disabled.

1. Move the cursor using arrows keys on field relative to “Integration period” , marked it

with blue background.

2. Press F4 key (alternatively touch the MODIFY at display). In the bottom of display a

command bar with “Integration Period” is shown.

3. Press F3 key (MOD(+)) or F4(MOD(-)) or up and down keys to set the desired

integration period choosing among the below values: 1s, 5s, 10s, 30s, 1min, 2min,
5min, 10min, 15min, 30min, 60min
.

4. Press SAVE key or ENTER key (or the smart icon

) to save the settings. The

integration period value is shown at display.


5.4.5. Cogenerations

The selection of this , effected both by using up or down arrows keys and directly selecting
the flag at display, enters the values of powers and energies generated (co-generation) in
the list of recorded parameters (see § 10.7.1).