Electrical connections – KROHNE OPTISONIC 7300 EN User Manual

Page 42

Advertising
background image

4

ELECTRICAL CONNECTIONS

42

OPTISONIC 7300

www.krohne.com

09/2012 - 4001102303 - MA OPTISONIC 7300 R03 en

Pulse/frequency output active, modular I/Os

• U

nom

= 24 VDC

• f

max

in the operating menu set to f

max

≤ 100 Hz:

I ≤ 20 mA
open:
I ≤ 0.05 mA
closed:
U

0, nom

= 24 V at I = 20 mA

• f

max

in operating menu set to 100 Hz < f

max

≤ 10 kHz:

I ≤ 20 mA
open:
I ≤ 0.05 mA
closed:
U

0, nom

= 22.5 V at I = 1 mA

U

0, nom

= 21.5 V at I = 10 mA

U

0, nom

= 19 V at I = 20 mA

• If the following maximum load impedance R

L, max

is exceeded, the load impedance R

L

must

be reduced accordingly by parallel connection of R:
f ≤ 100 Hz: R

L, max

= 47 kΩ

f ≤ 1 kHz: R

L, max

= 10 kΩ

f ≤ 10 kHz: R

L, max

= 1 kΩ

• The minimum load impedance R

L, min

is calculated as follows:

R

L, min

= (U

ext

- U

0

) / I

max

• X designates the connection terminals A, B or D, depending on the version of the signal

converter.

INFORMATION!

•

For frequencies above 100 Hz, shielded cables are to be used in order to reduce effects from
electrical interferences (EMC).

•

Compact and field housing versions:

Compact and field housing versions:

Compact and field housing versions:

Compact and field housing versions: Shield connected via the cable terminals in the terminal
compartment.
Wall-mounted version:

Wall-mounted version:

Wall-mounted version:

Wall-mounted version: Shield connected using 6.3 mm / 0.25" push-on connectors
(insulation to DIN 46245) in the terminal compartment.

•

Any connection polarity.

Figure 4-13: Pulse / frequency output active P

a