Electrical connections – KROHNE OPTISONIC 7300 EN User Manual

Page 44

Advertising
background image

4

ELECTRICAL CONNECTIONS

44

OPTISONIC 7300

www.krohne.com

09/2012 - 4001102303 - MA OPTISONIC 7300 R03 en

Pulse and frequency output passive P

N

NAMUR, modular I/O

• Connection in conformity with EN 60947-5-6
• open:

I

nom

= 0.6 mA

closed:
I

nom

= 3.8 mA

• X designates the connection terminals A, B or D, depending on the version of the signal

converter.

INFORMATION!

•

For frequencies above 100 Hz, shielded cables are to be used in order to reduce effects from
electrical interferences (EMC).

•

Compact and field housing versions:

Compact and field housing versions:

Compact and field housing versions:

Compact and field housing versions: Shield connected via the cable terminals in the terminal
compartment.
Wall-mounted version:

Wall-mounted version:

Wall-mounted version:

Wall-mounted version: Shield connected using 6.3 mm / 0.25" push-on connectors
(insulation to DIN 46245) in the terminal compartment.

•

Any connection polarity.

Figure 4-15: Pulse and frequency output passive P

N

to NAMUR EN 60947-5-6

Advertising