INSTALLATION
3
49
OPTIFLEX 1300 C
www.krohne.com
03/2014 - 4000172306 - HB OPTIFLEX 1300 R07 en
3.8.7 Recommendations for pits and tanks made of non-conductive materials
If you have a device with a single rod or a single cable probe and a thread connection,
obey these instructions:
• Put a metal sheet between the device and the process connection.
i
It must have a diameter greater than 200 mm / 8¨.
• Make sure that the metal sheet is in contact with the thread stop on the device.
We recommend that you use DN≥200 / ≥8¨ for flange connections.
If you have a device with a double rod, double cable or coaxial probe, you can ignore these
instructions.
Figure 3-40: Installation in a non-metallic tank or pit with a thread connection
1 Non-metallic (plastic...) tank or pit
2 Metal sheet, Ø ≥200 mm / 8¨
CAUTION!
When the device is installed, make sure that the tank roof has no deformation.