Electrical connections, 5 networks, 1 general information – KROHNE OPTIFLEX 1300C EN User Manual
Page 59: 2 point-to-point networks

ELECTRICAL CONNECTIONS
4
59
OPTIFLEX 1300 C
www.krohne.com
03/2014 - 4000172306 - HB OPTIFLEX 1300 R07 en
4.5 Networks
4.5.1 General information
The device uses the HART
®
communication protocol. This protocol agrees with the HART
®
Communication Foundation standard. The device can be connected point-to-point. It can also
operate in a multi-drop network of up to 15 devices.
The device output is factory-set to communicate point-to-point. To change the communication
mode from point-to-point
point-to-point
point-to-point
point-to-point to multi-drop
multi-drop
multi-drop
multi-drop, refer to
Network configuration
on page 86.
4.5.2 Point-to-point networks
Figure 4-4: Point-to-point connection (non-Ex)
1 Address of the device (0 for a point-to-point connection)
2 4...20 mA + HART
®
3 Resistor for HART
®
communication
4 Power supply
5 HART
®
modem
6 HART
®
communication device