8.4
Table of settable functions (Versions 4.04 – 4.06)
Function (Fct.)
Enter range
Default
value
Description
1.0 OPERATION
1.1 DISPLAY
LEVEL
DISTANCE
CONVERSION
1.1.1
FCT.DISP
Options
REFLECTION
LEVEL
Select function of
display
(value to be displayed).
m
cm
mm
inch
Ft
PERCENT
1.1.2
UNIT.LENGTH Options
BARGRAPH
Meter [m]
Select unit for value of
length to be displayed
(level/distance).
m3
l
US Gal
GB Gal
Ft3
bbl
PERCENT
BARGRAPH
1.1.3 UNIT. CONV
Options
USER UNIT
Cubic meter
[m3]
Select unit for
conversion value to be
displayed ("volume
table").
2.0 TEST
2.1 HARDWARE
2.1.1 MASTER
Special function
Tests the hardware of
the master.
2.1.2 DISPLAY
Special function
Tests the hardware of
the display.
Options
Module DIS
2.1.3
STATUS
Module
MW
Displays
ID-Number
and Status Bytes
2.2 CUR.OUTP.I
2.2.1
VALUE I
Value display
Displays the actual
value of the current
output.
Options 2
mA
4
mA
6
mA
8
mA
10
mA
12
mA
14
mA
16
mA
18
mA
20
mA
2.2.2
TEST
I
22
mA
2 mA
Output of selected
value to the current
output.
IMPORTANT !!! With
safety inquiry because
of direct access to the
current output !!!
(Exi = min. 3.6 mA)