8.5.1 Level

measurement

(example)

Tank height

(Fct. 3.1.1)

6.00 m

Antenna extension

(Fct. 3.1.4)

0.20 m

Block distance

(Fct. 3.1.2)

0.70 m

Response threshold or
maximum measurable level =
5.30 m (calculated from lower
reference point)

= tank height - block distance
(Fct. 3.1.1) (Fct. 3.1.2)

= 6.00 m - 0.70 m

Function I (Fct 3.3.1)

LEVEL

Range I (Fct. 3.3.2)

4 - 20 mA

Scaling 4 mA (Fct. 3.3.3)

0.00 m, equivalent to 4 mA

Current output I

Scaling 20 mA (Fct. 3.3.4)

5.00 m, equivalent to 20 mA

Function S (Fct. 3.6.1)

LEVEL

Type S (Fct. 3.6.2)

LOW (= below threshold)

Threshold (Fct. 3.6.3)

5.00 m

Switching output

Hysteresis (Fct. 3.6.4)

0.10 m

Function, display (Fct. 3.2.1)

LEVEL

Display

Unit, length (Fct. 3.2.2)

m (meters)

Note:

Display and outputs can also be used for different measured variables,
e.g.: display for conversion, current output I for level, and switching output S for
error messages.
The value for Scaling 20 mA should not be greater than the response threshold.

8.5.2 Volume measurement (example)

•

In order to be able to measure volume with the BM 70 M, a conversion table (volume table)
needs to be compiled with the PC-CAT program (see Sect. 8.12).

•

By means of the volume table, various levels are allocated to specific volumes previously
calculated or measured out.

•

In the case of non-symmetrical tanks, e.g. tanks with dished bottom, the accuracy of volume
measurement will depend on the number of set "level/volume pairs". The maximum number of
pairs (points) that can be set is 50; the volume is linearly determined (interpolated) between 2
points.

In the following example, 4 data pairs have been programmed:

Volume table

Unit volume (Fct. 3.2.3): m3

Point Level Volume
1

0.00 m

0.25 m³

2

0.25 m

0.70 m³

3

0.50 m

1.40 m³

Set table (PC-CAT)

4

5.30 m

16.80 m³

Tank height (Fct. 3.1.1):

6.00 m

Antenna extension (Fct. 3.1.6)

0.20 m

Block distance (Fct. 3.1.2)

0.70 m

Response threshold,
maximum measurable level
= 5.30 m, equivalent to a
volume of 16.80 m ³
(calculated from lower
reference point)

= tank height - block distance
(Fct. 3.1.1) (Fct. 3.1.2)
= 6,00 m - 0,70 m