Fct. 3.6.1. FUNCTION S

Use this function to select the measured variable.

•

OFF (= deactivated; Fct. 3.6.2, 3.6.3 and 3.6.4 are no longer selectable,
i.e. they are skipped over).

•

LEVEL

•

DISTANCE

•

CONVERSION

•

REFLECTION

•

ERROR OPEN (default)

•

ERROR CLOSED

(Explanatory notes: see Table overleaf)

Fct. 3.6.2. TYPE S

•

This function is not shown (is skipped over) when OFF or ERROR OPEN or ERROR CLOSED
is set under Fct. 3.6.1. Not significant is this case!

•

Use this function to set the type of switching output:
HIGH (= contact closes when upper limit of threshold + hysteresis / 2) exceeded
LOW (= contact closes when lower limit of threshold - hysteresis / 2) exceeded.

Fct. 3.6.3 THRESHOLD

•

This function is not shown (is skipped over) when OFF, ERROR OPEN or ERROR CLOSED
is set under Fct. 3.6.1. Not significant in this case!

•

Use this function to define the threshold (limit value).

•

Setting of LEVEL or DISTANCE under Fct. 3.6.1:
Unit same as for Fct. 3.1.1 TANKHEIGHT. If a reference or tank bottom offset is set, this must
be taken into consideration!

•

Setting: CONVERSION under Fct. 3.6.1:
Unit same as in Fct. 3.2.3 UNIT.CONV.

•

Setting: REFLECTION under Fct. 3.6.1:
Setting range : 0...100.

Fct. 3.6.4 HYSTERESIS

•

This function is not shown (is skipped over) when OFF, ERROR OPEN or ERROR CLOSED
is set under Fct. 3.6.1. Not significant in this case!

•

Use this function to define the hysteresis.

•

Setting: LEVEL or DISTANCE under Fct. 3.6.1:
Setting range and unit same as for Fct. 3.1.1 TANKHEIGHT.

•

Setting CONVERSION under Fct. 3.6.1:
Unit same as in Fct. 3.2.3 UNIT.CONV.

•

Setting REFLECTION under Fct. 3.6.1:
Setting range: 0...100.

Examples of application and setting see Sect. 8.5