KROHNE UFC 500 HART User Manual
Page 18
Advertising
HARTô Smart Communications Protocol
UFC500 Command Specification Rev: 2.0 Release Date: 9 Jun 2001
© 2001 KROHNE Mefltechnik D-47058 Duisburg
Page
18
8.4
Command #133
Write Frequency/Pulse Output Damping Control
Defines the damping value to be used on device frequency/pulse output.
REQUEST DATA BYTES
#0
FREQ/PULSE
DAMPING
CONTROL
RESPONSE DATA BYTES
#0
FREQ/PULSE
DAMPING
CONTROL
Data Byte #0
Damping control for the frequency/pulse output:
0 - Damping value is fixed to 40 ms,
Any other value - The same as for current output (Primary Variable Damping Value).
COMMAND-SPECIFIC RESPONSE CODES
0
No Command-Specific Errors
1-4
Undefined
5
Too Few Data Bytes Received
6
Local Device User
7
In Write Protect Mode
8-127
Undefined