HARTô Smart Communications Protocol

UFC500 Command Specification Rev: 2.0 Release Date: 9 Jun 2001

© 2001 KROHNE Mefltechnik D-47058 Duisburg

Page

43

8.23

Command #157

Write Device-Specific Units And Enumerators

Writes device-specific units and controls.

REQUEST DATA BYTES

#0

#1

#2

#3

PLAUSIB

NUMBER

NUMBER

WEIGHT

ERROR

PLAUSIB

PLAUSIB

POINT

ERRORS

ERRORS

OK

MSB

LSB

#4

#5

PULSE

PULSE

VOLUME

RATE

UNITS

UNITS

#6

#7

#8

#9

REV

DISPLAY

ERROR

DISPLAY

SCALE

TOTAL

MESSAGE

TRANSIT

CONTROL

CONTROL

CONTROL

TIME
CONTROL

RESPONSE DATA BYTES

#0

#1

#2

#3

PLAUSIB

NUMBER

NUMBER

WEIGHT

ERROR

PLAUSIB

PLAUSIB

POINT

ERRORS

ERRORS

OK

MSB

LSB

#4

#5

PULSE

PULSE

VOLUME

RATE

UNITS

UNITS

#6

#7

#8

#9

REV

DISPLAY

ERROR

DISPLAY

SCALE

TOTAL

MESSAGE

TRANSIT

CONTROL

CONTROL

CONTROL

TIME
CONTROL

Data Byte #0

Error limit in % of measured value for plausibility statement. Valid range: 1..99.

Data Byte #1..#2

Limit value for the counter of incorrect measurements. Valid range: 0..10000.

Data Byte #3

Weight factor for correct measurements. Valid range: 1..50.

Data Byte #4

Pulses per volume units, used only for scaling of PulseVolume parameter (refer to Command
#142, Read Frequency/Pulse Output Parameters) and do not affect physical output. For unitsí
codes refer to Table 9.3.

Data Byte #5

Pulse rate units, used only for scaling of PulseRate parameter (refer to Command #142, Read
Frequency/Pulse Output Parameters) and do not affect physical output. For unitsí codes refer
to Table 9.4.

Data Byte #6

Reverse scale control, defines whether the Upper Range Value for reverse flow is the same as
for forward, or different:
0 - Different,
1 - Same as for forward flow.
In the first case the Upper Range Value for reverse flow can be accessed via Command
#158, Read Transmitter Variable Range Values.