8.23
Command #157
Write Device-Specific Units And Enumerators
Writes device-specific units and controls.
REQUEST DATA BYTES
#0
#1
#2
#3
PLAUSIB
NUMBER
NUMBER
WEIGHT
ERROR
PLAUSIB
PLAUSIB
POINT
ERRORS
ERRORS
OK
MSB
LSB
#4
#5
PULSE
PULSE
VOLUME
RATE
UNITS
UNITS
#6
#7
#8
#9
REV
DISPLAY
ERROR
DISPLAY
SCALE
TOTAL
MESSAGE
TRANSIT
CONTROL
CONTROL
CONTROL
TIME
CONTROL
RESPONSE DATA BYTES
#0
#1
#2
#3
PLAUSIB
NUMBER
NUMBER
WEIGHT
ERROR
PLAUSIB
PLAUSIB
POINT
ERRORS
ERRORS
OK
MSB
LSB
#4
#5
PULSE
PULSE
VOLUME
RATE
UNITS
UNITS
#6
#7
#8
#9
REV
DISPLAY
ERROR
DISPLAY
SCALE
TOTAL
MESSAGE
TRANSIT
CONTROL
CONTROL
CONTROL
TIME
CONTROL
Data Byte #0
Error limit in % of measured value for plausibility statement. Valid range: 1..99.
Data Byte #1..#2
Limit value for the counter of incorrect measurements. Valid range: 0..10000.
Data Byte #3
Weight factor for correct measurements. Valid range: 1..50.
Data Byte #4
Pulses per volume units, used only for scaling of PulseVolume parameter (refer to Command
#142, Read Frequency/Pulse Output Parameters) and do not affect physical output. For unitsí
codes refer to Table 9.3.
Data Byte #5
Pulse rate units, used only for scaling of PulseRate parameter (refer to Command #142, Read
Frequency/Pulse Output Parameters) and do not affect physical output. For unitsí codes refer
to Table 9.4.
Data Byte #6
Reverse scale control, defines whether the Upper Range Value for reverse flow is the same as
for forward, or different:
0 - Different,
1 - Same as for forward flow.
In the first case the Upper Range Value for reverse flow can be accessed via Command
#158, Read Transmitter Variable Range Values.